A single-bottom elevator jack is a buried hydraulic cylinder closed by one welded bottom plate, so one weld and one steel piece hold both the oil and the car.
Florida sets no calendar deadline to replace one.
It does adopt a safety code that treats a buried single-bottom cylinder as something you have to correct, and replacement is only one of three ways to do that.
Most building owners hear “no deadline” and assume “no obligation,” and that is the expensive misreading.
What Makes A Single-Bottom Jack Different
A steel tube sits in the ground below the pit, and a plunger inside it pushes the car up.
On a single-bottom unit, one welded plate closes the bottom of that tube.
If the plate or its weld fails, there is no second barrier. The oil leaves, and the car descends. That is the entire concern.
A double-bottom cylinder adds a second plate above the first, plus a bulkhead with a restricted orifice.
If the outer shell corrodes through, the inner bulkhead holds pressure and the car settles slowly instead of dropping.
Does Florida Require Replacing A Single-Bottom Elevator Jack?
No rule gives you a date by which a working single-bottom elevator jack must be removed from the ground. But doing nothing indefinitely is not a compliant position either.
Florida adopts the ASME elevator safety code by rule, in Chapter 61C-5 of the Florida Administrative Code.
Florida currently enforces ASME A17.1-2019, A17.3-2020, and A18.1-2020 under the May 25, 2026 adoption, matching the 9th edition of the Florida Building Code.
For buried cylinders, the governing clause is A17.1 Section 8.6.5.8 (Safety Bulkhead), which applies to existing elevators, not just new installations, and offers three compliance paths: a cylinder that meets the new-elevator requirement in 3.18.3.4, car safeties with conforming guide rails and fastenings, or a plunger gripper that engages at governor tripping speed.
In short, there’s no deadline but also no permanent exemption, and the right path depends on your hoistway’s engineering, not just budget, since the cheapest option isn’t always feasible.
Code editions and enforcement can change, so confirm the requirement for your specific unit with your elevator contractor and building official before committing funds.
Who Actually Enforces This Where You Are
This surprises people. The Bureau of Elevator Safety holds no-cost service contracts with five local jurisdictions that run annual inspections, issue certificates of operation, review plans, and enforce code in their own areas.
Those five are the City of Miami, Miami Beach, Miami-Dade, Broward, and the Central Florida Tourism Oversight District.
If your property sits in any of them, the office writing up your elevator is local, and their bulletins and advisories carry real weight.
Miami-Dade’s elevator safety office took the position years ago that the state statute letting an elevator follow the code in effect when its permit is issued does not excuse an owner from retrofit requirements adopted later for safety reasons.
In practice, that means an inspector can cite a buried single-bottom cylinder, and the office can order the unit out of service until it is corrected.
The state, through the Florida Department of Business and Professional Regulation, licenses elevator professionals.
Why Buried Cylinders Fail Faster In South Florida
Most of these jacks went in with a PVC sleeve and little else between steel and earth. The design assumed dry soil.
The water table here sits close to the surface, the groundwater carries salt, and a sleeve cracked during installation lets both reach the cylinder.
Corrosion works from the outside in, so the unit looks fine from the pit until it does not.
Three patterns show up again and again on older units:
- A sleeve never sealed at the top, so pit water ran down the outside of the cylinder for decades.
- Oil loss with no wet spot in the pit, because the fluid went into the soil instead of the floor.
- A reservoir topped off for years without anyone asking where the oil went.
That third one is the costly mistake. Every gallon added to a leaking buried jack is a gallon in the ground, and the cleanup obligation is separate from the repair.
Buildings across Miami Beach elevator service territory tend to carry the longest version of this history.
How To Find Out What You Have
You cannot tell from the pit, because the relevant part is underground.
Start with the original installation paperwork or layout drawings, which often state the cylinder type.
If those are gone, your maintenance provider may have it in the unit history, and a prior jack replacement would appear in permit records.
The symptom to take seriously is oil loss you cannot account for in the pit. Treat that as a buried leak until somebody proves otherwise.
What The Correction Project Actually Involves
Replacing the cylinder, or adding a safety bulkhead, is an alteration, not a repair.
The state’s Bureau of Elevator Safety said so in a technical advisory, and the consequence is concrete: the work goes in under permit, and the car must be tested with full rated load before it carries the public again.
Budget the parts people forget:
- Permit and inspection time, which runs on the jurisdiction’s calendar.
- Pit waterproofing, because a new cylinder in the same wet hole repeats the failure.
- Soil assessment if oil was lost underground.
- Downtime for that elevator, or the bank if you stage the work.
Since the pit is already open, this is the cheapest moment to handle jack head replacement and packing.
It is also the moment to ask whether a holeless unit fits your hoistway instead of another buried cylinder.
A new jack also changes leveling and ride quality, as covered in what a new jack changes.
Florida does attach hard dates to some other retrofits, which is why owners confuse the two.
The door lock monitoring deadline is a dated requirement. Buried cylinders are not.
One limit: none of this applies to traction elevators or to holeless hydraulic units with above-ground jacks. There is no buried cylinder in play.
Start With The Permit History, Not A Quote
Pull your building’s elevator permit records before you call anyone for a price.
If a cylinder replacement shows up, you likely already have a double-bottom unit.
If nothing shows and the building is old enough, assume single-bottom and put it on the capital plan instead of discovering it during an outage.
We can confirm cylinder type, lay out which of the three compliance paths your hoistway supports, and bring the work in under elevator code compliance.
The wider state picture sits in Florida elevator safety rules.